SERIES
COIL INDICATION AND MODULE PROTECTION FACILITIES
-
LED module: to indicate presence of voltage across coil DIODE module: to protect coil from back EMF LED + DIODE module: to indicate presence of voltage across coil and protect coil from back EMF LED + varistor module: to indicate presence of voltage across coil and protect coil from back EMF RC circuit module
87
99.01 DIODE MODULE
A1
99.44 FUNCTIONS OPERATING RANGE
99.73 CODE CODE CODE
99.80 CODE
+ -A2 D
Recovery diode modules are used for DC only. The negative cut-off voltage peaks of the coil are short circuited by the recovery diode 6 - 220 V DC (positive to terminal A1). The drop-out time increases by an approximate factor of 3. If an increase of the drop-out time is not wanted use a Varistor or RC module. Recovery diode modules are used for DC only. The negative cut-off voltage peaks of the coil are short circuited by the recovery diode (positive to terminal A2). The drop-out time 6 - 220 V DC increases by an approximate factor of 3. If an increase of the drop-out time is not wanted use a Varistor or RC module.
9901.3000.00 9944.3000.00 9973.3000.00 9980.3000.00
DIODE INVERTED POLARITY
A1
-+
A2 D
9901.2000.00 9944.2000.00
--
--
LED MODULE
A1 D
+ -A2 R
LED modules are used for AC and DC. The LED indicator lights up when the coil is energized. When using DC it is essential that positive LD is connected to terminal A1.
6 - 24 V DC/AC 9901.0024.59 9944.0024.59 9973.0024.59 9980.0024.59 28 - 60 V DC/AC 9901.0060.59 9944.0060.59 9973.0060.59 9980.0060.59 110 - 230 V DC/AC 9901.0230.59 9944.0230.59 9973.0230.59 9980.0230.59
DIODE MODULE + LED
A1 D Recovery diode modules + LED are for DC only. The negative cut-off voltage peaks of the coil are short circuited by the recovery diode 6 - 24 V DC (positive to terminal A1). The drop-out time 28 - 60 V DC increases by an approximate factor of 3. LD 110 - 220 V DC If an increase of the drop-out time is not wanted use a Varistor or RC module. The LED indicator lights up when the coil is energized.
+
D
-A2
R
9901.9024.99 9944.9024.99 9973.9024.99 9980.9024.99 9901.9060.99 9944.9060.99 9973.9060.99 9980.9060.99 9901.9220.99 9944.9220.99 9973.9220.99 9980.9220.99
DIODE MODULE + LED INVERTED POLARITY
A1 D
-+
D R A2
Recovery diode modules + LED are for DC only. The negative cut-off voltage peaks of the coil 6 - 24 V DC are short circuited by the recovery diode (positive to terminal A2). The drop-out time 28 - 60 V DC increases by an approximate factor of 3. 110 - 220 V DC LD If an increase of the drop-out time is not wanted use a Varistor or RC module. The LED indicator lights up when the coil is energized.
9901.9024.79 9944.9024.79 9901.9060.79 9944.9060.79 9901.9220.79 9944.9220.79
--
--
LED MODULE + VARISTOR
A1 D VDR
+ -A2 R
LED modules + Varistor are used for both AC and DC coils. The cut-off voltage peaks of the relay coil are limited by the Varistor to approximately 2.5 times the nominal voltage LD of the module. When using DC coils it is essential that positive is connected to terminal A1. The relay drop-out time increases only insignificantly.
6 - 24 V AC/DC 9901.0024.98 9944.0024.98 9973.0024.98 9980.0024.98 28 - 60 V AC/DC 9901.0060.98 9944.0060.98 9973.0060.98 9980.0060.98 110 - 230 V AC/DC 9901.0230.98 9944.0230.98 9973.0230.98 9980.0230.98
RC MODULE
C Rc circuit modules are used for AC and DC coils. The cut-off voltage peaks of the relay 9901.0024.09 9944.0024.09 9973.0024.09 9980.0024.09 are limited by the RC module to approximately 6 - 24 V AC/DC 9901.0060.09 9944.0060.09 9973.0060.09 9980.0060.09 2.5 times the nominal voltage of the modules. 28 - 60 V AC/DC The relay drop-out time increases only 110 - 230 V AC/DC 9901.0230.09 9944.0230.09 9973.0230.09 9980.0230.09 insignificantly.
R
REMANENCE
Bypass modules are advisable, if the relay coils do not drop-out between 110-240 V AC. Failure to drop-out can be caused by residual 110 - 230 V AC R currents from AC proximity switches or inductance couplings caused through long parallel lying AC control lines.
9901.8230.07 9944.8230.07 9973.8230.07 9980.8230.07
88


▲Up To Search▲   

 
Price & Availability of 9901-0024

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X